What is Mixing?
Mixing is when a portion of return water from the system is mixed with a
portion of hot water from the boiler to supply a specific water temperature that is lower
than the boiler temperature but warmer than the return temperature.What methods
are used for mixing?
There are two basic mixing methods: mixing valves which consist of three-way and four-way
valves, and injection mixing which uses either two-way valves or injection pumps.
What is the difference between each method?
A three-way mixing valve has three ports and a four-way valve has four ports. Mixing
blends cooler return water into one of the valves ports with hot water that is
entering another port. The two temperatures blend and exit the supply port. With a
four-way valve, any of the return water that isnt used to mix with the hot water is
returned back to the boiler. Injection mixing injects bursts of hot water into a
constantly circulating loop. A two-way valve opens and closes, or a pumps speed is
changed, to introduce the right amount of heat.
Why would someone use mixing in a hydronic system? Three major uses, for:
· Radiant heating that requires lower water
temperatures than most boilers can produce without experiencing flue gas condensation.
· Outdoor reset. By matching the supply
water temperature to the load on the building, the heating system will operate more
efficiently. Unfortunately, the required water temperatures are lower than most boilers
are designed to handle.
· Hydronic systems that incorporate
different types of heat emitters such as in-floor heating, panel radiation, cast-iron
radiation and hydroair coils. Each type requires a different supply temperature but all
receive their water from the same boiler.
What happens if I use only one pump with my mixing device?
There will be only one mixing point. This will control the supply water temperature for
that particular zone, but not the temperature of the water returning to the boiler. Also,
the flow rate through the boiler will vary, decreasing the boilers efficiency.
Why should I use two pumps?
Using two pumps, with a mixing device, establishes two mixing points. This protects the
boiler by controlling the temperature of the returning water. The second pump also
provides constant flow through the boiler, improving the boilers efficiency. How
should I pipe the mixing device and the two pumps? Use primary/secondary pumping so the
two pumps will not operate in series with each other. Another benefit of primary/secondary
pumping: you can efficiently size the mixing device.
Why should I be concerned with the temperature of the water returning to the boiler?
If you are using a non-condensing style boiler, it is important that the flue gases
released from the combustion process be vented out of the boiler. When the water in the
boiler is at a temperature below the dewpoint of the flue gases, these gases will condense
back to water inside the boiler. The results can be very damaging. Boiler thermal shock is
another reason for controlling the return temperature.
What is flue gas condensation?
During combustion of the fuel, many byproducts are formed including carbon dioxide, sul-
phur compounds and water vapor. Low return water temperatures will cause the compounds to
condense, forming corrosive liquids in the boiler stack and heat exchangers. The amount of
damage that will occur depends on the design and materials of construction used in the
boiler, as well as the specific compounds in the flue gas. Always check with the boiler
manufacturer to find the minimum recommended return water temperature.
When using a mixing device, how do I calculate the flow rates to achieve the
desired mixed temperature?
The answer can be found in this example:
Radiant zone load = 50,000 Btu/h designed at 20° temperature drop.
Design radiant zone flow rate = 5gpm
Radiant design supply temperature = 120°F (based upon 20°F temp. drop, return temp. of
100°F)
Boiler loop supply temperature = 180°F
The design temperature difference between the two loops is 80°F so 50,000 :
( 80°F x 500 ) = 1.25 gpm
This is the amount of 180°F boiler water needed to mix with 3.75 gpm of
100°F return water from the radiant zone to supply 5 gpm of 120°F water.
For answers to any hydronic heating question, contact your Bell & Gossett
representative.
Reprinted from CounterPoint May 1999, Vol. 6, Issue 1