| Tower pumping does not present great difficulty in terms
of good pump application. This is because of a normally high order of application safety
factors. Troubles do occur occasionally, however. So,
lets take a look at these potential troubles and see how to solve them.
Pump Head Requirements
The pumping head determination
procedure for the open tower piping loop differs from the conventional
closed loop piping circuit used for most hydronic (heat-cool) applications.
The difference concerns consideration of open loop static heads.
The closed loop circuit has no need for consideration of
static heads for pump selection because of a balance or cancellation of static heads
between the supply and return risers. Static head lost by water flow to any height in the
supply piping is cancelled by a static head regain as water flows down the
return piping. The only pump head requirement for the closed loop is that due
to flow-friction pressure drop, (Fig 1).
The open or tower circuit is different from the
closed loop circuit in that all static heads are not cancelable. In the open
piping circuit, the pump must raise fluid from a low reference level to a higher level;
this requires pump work, and open statics becomes an important consideration for pump
selection.
In Fig. 2, the required pump
head will be the pipe flow-friction loss from A to D plus the energy head (Hs) required to
raise water from the lower to higher level.
The cooling tower circuit differs slightly from the basic
open circuit in that the discharge piping is seldom connected directly to a
discharge tank. The tower discharge is generally to the atmosphere and then into a
distribution pan.
For the tower piping circuit, the pump must overcome the
piping flow friction loss: piping, condenser, valves, etc. It must also provide the energy
head necessary to raise water from a low to a higher static head level.
Most discussions concerning tower and/or open piping
circuits would simply define the required pump static energy head as Ho (see Fig.
3)the open height of the piping circuit. This is, however, an
over-simplified assumption which may or may not be true depending on whether or not a
siphon draw is established in the downcomer return piping, DE. The nature of
the downcomer siphon draw and its limitations should be evaluated.
Downcomer Siphon Draw
In Fig. 3, water is being discharged at E to the
atmosphere. Pressure at D must be equal to exit loss plus flow-friction loss DE and minus
the static pressure reduction caused by downcomer return static height Hr.

Pressure reduction to D as caused by static height Hr will
generally, but not always, permit cancellation of height Hr as a part of the required pump
head. This is because of a resultant siphon draw action in the downcomer.
Given that the siphon draw does indeed occur,
the required pump head will become:

The pump head selection statement shown above is commonly
accepted as a truism. It has limitations, however, and will not apply under certain
circumstances. These circumstances should be understood if unnecessary cost and
embarrassment are to be avoided by the consultant.
Exit loss and flow-friction loss in the downcomer will
generally be less than the downcomer height Hr. For this circumstance, the downcomer must
operate at sub-atmospheric pressure when the siphon draw is established. If the downcomer
vacuum is broken, the expected siphon draw will not occur, and the estimated pump head may
be inadequate.
The expected downcomer return siphon draw vacuum can be
broken by any of three basic application circumstances: 1. Top-vented downcomer. 2.
Inadequate downcomer flow rates; bottom-vented downcomer. 3. Fluid vapor pressure or flash
considerations.
Top-Vented Downcomer
A downcomer vent will break the siphon draw vacuum. The
vent may be a simple loose pipe connection, or it may be a mechanical vent purposefully
applied at the downcomer return high point.
Vents are sometimes applied to establish known reference
pumping conditions when downcomer return siphon draw conditions propose stability
problems, as with a very high downcomer, when fluid boiling is a probability, or when
start-up downcomer flow rates are anticipated as inadequate for the siphon draw.
Given a top-vented downcomer, the pump must raise water
from the pump suction pan water level to the highest vented point in the downcomer.
Considering this point to occur at D in Fig. 3, the
required pump static head will become Ho + Hr or Hs.
The total pumping head to point D will become Hs plus the
flow-friction loss Delta h (AD). Separate consideration must now be given to the downcomer
return.
Since the pump has raised water to level D, it
provided a fluid head equal to Hr to overcome flow-friction loss in the downcomer. There
are two different pumping possibilities; fluid head Hr greater than downcomer
flow-friction loss (Delta h DE) and the reverse: Hr less than Delta h (DE).
The usual pumping circumstance will be the condition of Hr
greater than Delta h (DE). This is because the available fluid head Hr is the equivalent
of 100 ft./100 ft. pipe friction loss rate. Downcomer piping flow-friction loss will
generally be to the order of 4 ft./100 ft. Since the pump has already provided the
necessary fluid head to flow the downcomer, Hr > Delta h (DE); friction-flow loss in
the downcomer is not a part of the required pump head, and total pump head becomes:

High downcomer pressure drops can be caused by control
valves or tower spray nozzles. When this pressure drop plus the downcomer pipe
flow-friction loss exceeds fluid head Hr, the pump head must be increased by the
difference Delta h (DE) minus Hr. Total pump head then becomes:

Bottom-Vented Downcomer
Downcomer flow rates can be so low, relative to pipe size,
as to allow air to enter at the pipe discharge, causing the downcomer to become vented and
will prevent formation of the necessary siphon draw vacuum. Tests conducted at Bell &
Gossett indicate the siphon draw will not be established when the actual flow-friction
loss rate is less than the order of 1/100 based on clean pipe pressure drop
evaluation.
Pump head requirements for the bottom-vented downcomer will
be as previously noted for the top-vented circumstance.
An unfortunate operational sequence can occur during pump
start-up when the pump energy head is devoted towards simply raising water from the low
level pan to the highest part of the system.
During this start-up period, flow rates can be so low as to
cause bottom venting and prevent (sometimes forever) formation of siphon draw
circumstances and full design flow rates. A water-legged discharge or discharge reducer
will provide automatic siphon draw establishment so long as minimum start-up
flow velocity in the downcomer is to the order of 1 ft./sec.
In Fig. 4, air entry into the pipe discharge is prevented.
The minimum flow velocity pulls air bubbles down the piping, finally evacuating the
downcomer of air and establishing the siphon draw conditiondowncomer pipe full of
water and operating at sub-atmospheric pressure.

Unusual application circumstances will sometimes establish
such a low start-up flow rate (less than l/sec. velocity) that air bubbles are not
carried down the piping. The downcomer cannot then be emptied of air and expected siphon
draw will never occur.
For this circumstance, it is necessary to separately fill
the downcomer with water. This can be accomplished by valve closure at the piping exit in
combination with a top vent. During start-up, the exit valve is closed and the vent
opened. After the piping is filled, the vent is closed and the exit valve opened.
Siphon Draw Limitation
Given sufficiently low sub-atmospheric pressure, any fluid
will flash or boil. Fluid pressure in the downcomer piping cannot be less than the
pressure at which the fluid boils. Fluid vapor pressure thus provides a siphon draw
limitation.
Theoretical cancelable downcomer return static height (due
to sub-atmospheric siphon draw) will vary dependent on fluid vapor or boiling pressure and
on atmospheric pressure as this changes from sea level. The variation for water as
affected by water temperature and height above sea level is shown in Table I.
| Table 1: Maximum theoretical
downcomer return cancelable static height because of siphon draw: water only. |
| |
Water temperature °F |
| Height above sea level |
Cold |
105 |
120 |
140 |
160 |
180 |
200 |
| 0 |
34 |
31.8 |
30 |
27.6 |
23.4 |
17 |
7.7 |
| 1,000 |
32.8 |
30.1 |
29 |
26.4 |
22.2 |
15.8 |
6.4 |
| 2,000 |
31.6 |
29.1 |
28 |
25.3 |
21 |
14.6 |
5.2 |
| 3,000 |
30.2 |
28.2 |
26.8 |
24.1 |
19.9 |
13.5 |
4.03 |
| 4,000 |
29.2 |
27 |
25.6 |
23 |
18.7 |
12.2 |
2.82 |
| 5,000 |
28 |
25.6 |
24.4 |
21.8 |
17.5 |
11.1 |
1.61 |
| 6,000 |
26.9 |
24.6 |
23.2 |
20.6 |
16.4 |
10 |
.48 |
| 7,000 |
25.8 |
23.4 |
22.2 |
19.4 |
15.2 |
8.8 |
|
| 8,000 |
24.6 |
22.2 |
21 |
18.2 |
14 |
7.6 |
|
| 9,000 |
23.4 |
21.2 |
19.8 |
17.1 |
12.9 |
6.4 |
|
| 10,000 |
22.2 |
19.9 |
18.6 |
15.9 |
11.7 |
5.2 |
|
Fig. 5 illustrates an example tower
schematic for an installation located at 6,000 ft. elevation. The tower is to be used to
dissipate heat from 180° water; what is the required pump head?

(The figures shown in Fig. 5 correspond to available fluid
head over and above vapor pressure for the water temperature shown.)
Reference to Table I shows that the cancelable siphon draw
height for 6,000 ft. elevation and 180° water is only 10, while downcomer return
static height is 30 ft.
If conventional pump selection practice were to be
followed, the pump selection would be:

This pump selection provides a perfect example of low
start-up flow rates; the pump head will just be enough to raise water to the system top.
Start-up flow rate will be insignificant.
Even given the special application precautions previously
stated, the pump selection wont work because water flash in the downcomer will
prevent establishment of the presumed 30 siphon draw head. In this instance, water
would flash because the downcomer return static height exceeds the cancelable siphon draw
head (see Table I: 6,000 ft. at 180° = 10).
When downcomer return height exceeds cancelable siphon draw
head, it is necessary to separately evaluate downcomer needs. For these circumstances the
summation of cancelable siphon draw static height plus downcomer return flow friction loss
must exceed downcomer return height; the excess providing anti-flash pressurization.
The necessary downcomer flow-friction loss would generally
be established by a balance valve positioned close to the outlet (E). This valve will now
provide the necessary back pressure to maintain downcomer fluid pressure at
above its boiling or vaporization point.
For the particular example, a valve pressure drop equal to
the order of 23 ft. would establish an overall downcomer return flow-friction loss of 25
ft. (23 + 2 = 25).
A 25 downcomer flow-friction loss added to the
theoretical cancelable height of 10 ft. will establish a pressure over and above boiling
of 5 ft. at D.

The correct pump head selection now becomes:

For this particular example, a simpler solution could apply
an open vent at D,eliminating need for the downcomer balance valve and its
setting. In this case, the pump provides an available head at D of 30.
This fluid head is available for downcomer flow and is greater than flow-friction loss in
the downcomer (Delta h DE) of 2. Downcomer return flow-friction loss can then be
neglected since downcomer fluid will be in free fall.
Required pump head would then become:

Either correct solution will provide required design flow
rates. Design flow rates would not and could not be established by the
conventional head selection of 40 ft.
This is an abridged version of an article based on Bulletin
No. TEH-1075, Cooling Tower Pumping & Piping that appeared in the November
1998 issue of Service & Contracting.
Reprinted from TechTalk January 1999
Copyright 1999 by ITT Industries |