Recently a contractor needed help with a job involving an
old two-pipe steam system. It was a real adventure. The mistake he made was classic and
one worth sharing with you. He described the problems he was having with the system:
"The building was heating unevenly and banging. I visited the building and discovered
that steam was pouring out of the vent pipe on the condensate pump." He figured
the banging was caused by all the excess steam coming from the receiver vent, and the
uneven heating was caused by the steam heading toward the vent line on the receiver
instead of traveling towards the radiators. He installed a float and thermostatic Bear
Trap right in front of the receivers inlet which stopped the steam from blowing out
the vent line, but the heating system continued to bang and heat unevenly. In fact, if
anything, after installing the trap the uneven heating became worse and the banging seemed
louder! He was under the gun because he assured the customer that he knew what the problem
was, and that he also knew the solution. At that point, the contractor called his Hoffman
representative for help.
We hear and see the contractors problem all the time. Other than
preventing the steam from blowing out the receivers vent pipe, his approach does
nothing to fix the real problem and it will likely make the problem worse! To understand
why his solution will not work, you must first understand how a two-pipe trapped system is
designed to work.
Steam is produced in the boiler and then heads out towards the radiation. In front of
the steam is air, which is always present and needs to be vented before the steam will
enter the mains and radiators. In a one-pipe system, the air is vented through the main
vent and the individual radiator vents. However, with a two-pipe system there are radiator
traps installed on the outlet side of each radiator. These traps perform several
functions.
They are normally open to vent air
from the radiator and pass it into the return system.
They snap shut in the presence of
steam, preventing it from getting into the return piping.
They open to drain the condensate
that forms when the steam in the radiator condenses.
The air that passes into the return piping is eventually vented out of the system
through the condensate pumps vent pipe. The system is designed to operate with steam
in the supply pipes and radiators, and only with air and condensate in the returns. As the
condensate forms in the mains and radiators, the traps open and allow it to gravity drain
back to the vented receiver. Once there, the float in the receiver rises and turns on the
pump. The condensate is forced back into the boiler to start the cycle all over.
The big difference between what we just described, and what our contractor friend saw,
is the steam blowing out the receivers vent pipe. The first question the contractor
should ask is: What would allow steam to show up at the condensate receivers vent
pipe? Remember that one of the functions of a steam trap is to trap steam! When it
doesnt, there is nothing to prevent the steam from crossing over into the return
side of the system and once there, the pressure in the return piping will start to
approach the same pressure as in the supply mains. This will stop the steam in its tracks
because it needs this pressure differential to move. Its like turning the circulator
off in a forced hot-water system and expecting the system to still operate. Try to think
of a two-pipe system as a ladder. One side of the ladder is the supply and each rung is a
radiator with a steam trap. The other side of the ladder sees only the air and condensate
from each rung.
When our contractor friend installed the "master trap" in front of the
condensate receivers inlet, he only made a bad situation worse. The float and
thermostatic (F&T) trap made sure that the returns would be pressurized. There was no
pressure differential across the systems original F&T traps, and this caused the
condensate to back up in the distribution mains, causing more problems. The solution to
this systems problem-and many others that plague two-pipe steam systems-is to
replace the radiator traps that have failed in the open position.
If you are experiencing problems with a steam system, or have any steam questions, give
your Hoffman / McDonnell & Miller Steam Team
representative a call.
Reprinted from CounterPoint November 1998, Vol. 5, Issue 2