The problem of "cavitating condenser water
pumps" with adequate NPSH available is not uncommon. We discussed this phenomenon
with cooling tower manufacturers and other centrifugal pump designer/manufacturer members
of the Hydraulic Institute. All agree that this phenomenon commonly concerns cooling tower
applications. We see on average one or two such cases per year. At this point, several
theories are offered to explain the cavitation-like noise, but none validated. These
facts, however, are known:
- The noise experienced is very similar, if not identical, to
classical cavitation (sounds like pumping marbles).
- The phenomenon can occur with either a forced draft or
induced draft cooling tower.
- The resulting noise tends to be more prevalent on
negative suction pressure systems but will occur on positive suction pressure as well.
- The introduction of small amounts of air to the pump
suction often reduces or eliminates the cavitation noise.
- Entrained air introduced as Number 4, above, has
little effect on the pump's life expectancy.
- Such small amounts of entrained air have little
deleterious effect on other tower system components; however, each system must be analyzed
for possible harmful effects.
- Unlike classic cavitation, throttling of the pump
discharge to a lower capacity usually has little impact on the noise level.
In an effort to determine the probable cause of the noise,
we made several visits to sites experiencing such problems. Typically a detailed site
inspection is conducted and an audible recording made of the noise spectra for laboratory
analysis. Subsequent analysis revealed the following:
- No distinct frequencies were found.
- The predominant noise measured was broad band, occurring
above 300Hz.
There are two mechanisms for generating pump noise: liquid
and mechanical. Both sources produce acoustic pressure fluctuations that can be
transmitted as audible noise.
For centrifugal pumps, mechanical noise is generally the
result of component imbalance (impeller and/or coupler), coupler misalignment, rubbing
components or improper installation of the base plate and/or motor. These mechanical
mechanisms generate distinct frequencies equal to rotational speed and/or multiples
(1,2,3) of rotational speed. Because the noise spectra did not reveal distinct
frequencies, we concluded the noise was not mechanically generated.
The second mechanism for generating noise is velocity of
the liquid entering the pump. Liquid noise is directly produced by water movement and is
fluid dynamic in character. Turbulence, flow separation (vortex), cavitation, water
hammer, flashing and impeller interaction with the volute cutwater are all examples of
fluid dynamic noise sources.
According to the Pump Handbook, 2nd Edition authored by
Igor J. Karassik, there are generally four types of pulsation sources in pumps that result
from liquid noise:
- Discrete frequency components generated by the pump impeller
- Broad-band turbulent energy resulting from high flow
velocities
- Impact noise consisting of intermittent bursts of
broad-band noise caused by cavitation, flashing and water hammer
- Flow-induced pulsations caused by periodic vortex
formation when flow is past obstructions and side branches in the piping system
Discrete frequencies, item I from above, can be ruled out
as the cause of the noise problem. As previously mentioned, distinct frequencies, such as
the vane passage frequency and/or its multiples, were not found. This would be the case if
an interaction occurred between the impeller and volute cutwater.
Item 2, 3 and 4 are generally identified as broad-band
noise and would occur in the 300 Hz and above frequency range as identified on our noise
spectra. Therefore, we believe the noise was being generated by one or more of these
liquid sources.
The pump noise observed is that of cavitation. Pump
cavitation results from the formation of vapor bubbles when the localized static pressure
is lower than the vapor pressure of the liquid being pumped. To evaluate the pump for
classic cavitation (NPSHR greater than NPSHA) close the discharge valve thus pushing the
pump back on its curve toward shut-off. The noise should diminish significantly if it
originated from classic cavitation, as lower pump flows require reduced NPSHR. If the
noise continues, entrained air may be the cause.
We knew classic cavitation was not occurring in one
particular installation because the operating suction pressure measured 30 feet above
vapor pressure. Thus, the NPSH available was approximately twice that required by the
pump. For that reason, we knew the pump is not cavitating because of insufficient NPSHA.
SO, if not classic cavitation,what was causing the noise?
It is a well-documented fact that highly aerated cooling
tower water can contain as much as 4-6% excess air. This excess air exacerbates the
potential for a noisy pumping installation. The excess air absorbed in the cooling tower
comes out of solution as it flows through the piping and becomes entrained air. Suction
velocities often are high enough to pass the air through. However, air sometimes collects
in an area of the suction piping and creates an obstruction (Figure 1). As the liquid
passes through this reduced area, its velocity increases, creating an area of reduced
pressure. At this point of reduced localized pressure, water vaporization occurs with the
resulting bubbles passing into the pump impeller where they collapse, and produce
"cavitation."
Several noise control techniques have been successfully
employed in the past to reduce excessive noise:
- Increase or decrease the pump speed to avoid system
resonances of the mechanical or liquid systems.
- Increase liquid pressures (NPSHA, etc.) to avoid
cavitation or flashing; decrease suction lift. This could include raising the tower,
lowering the pump, or straightening the suction piping (see below) to reduce friction
losses.
- Modify the pump so that the clearance between the
impeller diameter and casing cutwater (tongue) or diffuser vanes is increased.
- Inject a small quantity of air into the suction of a
centrifugal pump to reduce cavitation noises by providing a shock absorbing cushion to
minimize the impact of recondensation of water vapor within the pump impeller.
The injection of small amounts of air can usually be
accomplished quickly and easily in the field with minimal expense. Small amounts of
entrained air usually cause no problem in the cooling tower/condenser circuit. B&G
therefore considers this alternative desirable and recommends its application as a
solution to certain field problems or, at a minimum, as an analytical tool.
Contributing Factors
In addition to the techniques outlined above to reduce or eliminate noise,
attention must also be given to two other factors that can exacerbate noise problems:
vortexing of liquid in the tower pan, which is the most common source of entrained air,
and the suction piping arrangement itself.
Vortexing of Liquid in the Tower Pan The amount of entrained air caused by vortexing depends on
several variables, but particularly the vortex size and the submergence level of the pump
suction pipe below the water level of the pan. The most common method of eliminating
vortexing in the tower pan is by the inclusion of baffle assemblies to eliminate the
formation of vortexes. Raising the fluid level in the pan to sufficient depth also can
resolve this problem.
Suction Piping Coupled with the vortexing
phenomenon, or by itself, the improper layout of the pump suction piping can be a
significant contributor to the generation of pump noise.
Friction losses caused by undersized suction piping can
cause an increase in fluid velocities into the pump. The pipe friction can be reduced by
using pipe sizes that are one to two sizes larger than the pump suction nozzle. Suction
line velocities should never exceed 10 ft./sec. and should realistically be designed for 5
ft./sec. Suction headers should be designed for a maximum velocity of 3 ft./sec.
Concentric reducers used to step down to the pump flange
from the larger suction piping can also be a culprit if improperly installed. At one
problem facility discussed earlier in this article, the reducer was installed upside down
(Figure 1) with the flat side on the bottom. If the pump liquid contains air (or vapor),
as it did in that case, the air can become trapped in the sloped area of the reducer now
located on "top." As a minimum this will obstruct the flow passage causing
higher velocities and thus localized vaporization. If transported into the impeller, the
trapped air can create a momentary choking that could even cause shaft breakage.
Elbows used on the pump suction flange, while convenient,
can cause an uneven flow of liquid into the impeller when the elbow bend is along the axis
of the pump shaft. If the elbow is a short radius design, you may create enough turbulence
to produce entrainment which can, and does, exacerbate noise problems. The addition of a
second elbow only increases the problem, especially if it has been added in a position at
right angles to the first. Numerous technical publications, as well as the Hydraulic
Institute itself, state that a minimum of five pipe diameters of straight run of pipe
should be provided before the pump suction flange to allow for a smooth, unimpeded flow to
the impeller.
System strainers need to be located on the discharge side
of the tower pumps, and not on the suction side. On a different project, the location of
basket strainers directly in front of the suction flange on a large HSC pump resulted in
an unexpectedly high pressure drop. This turned out to be one of the contributing factors
to poor pump performance in that installation, as well as higher noise levels from the
pump.
It must be understood that each job site has its own
particular set of operational requirements and, therefore, there is no single solution to
the noise problems. The Hydraulic Institute is considering an HI standard design
recommendation to allow an ample margin of safety between NPSH available and the pump
manufacturer's published NPSH requirements. The margin of safety would be a minimum of 1.7
times NPSH required or NPSH required plus 5 feet, whichever is higher.
If you are experiencing noise problems and need some help
diagnosing the cause, contact your local Bell & Gossett Representative. |