When a heat exchanger "stalls," condensate
floods the steam space and causes a variety of problems within the exchanger:
Control hunting: As condensate backs up in the exchanger,
the heat transfer rate to the process is greatly reduced. The control valve opens wide
enough to allow flow into the exchanger. As condensate drains out, the steam space is now
greater and the steam pressure increases. The process overheats, the control valve closes
down, and the cycle repeats.
Temperature
shock: Condensate backed up inside the steam space cools the tubes that carry the process
fluid. When this sub-cooled condensate is suddenly replaced by hot steam due to poor steam
trap operations, the expansion and contraction of the tubes stress the tube joints.
Constantly repeating this cycle causes premature failure.
Corrosion
from:
Flooding - A flooded heat exchanger will permit the oxygen to
dissolve, as well as carbon dioxide and other gases found in the steam. Because the
condensate is often sub-cooled due to the time it is in the exchanger, these gases are
more readily dissolved. Together the cool condensate and dissolved gases are extremely
corrosive and will tend to decrease the efficiency of the heat exchanger and reduce the
heat transfer through the tubes.
Steam collapse - Under very low loads with the steam valve closed, the
steam volume collapses to smaller volume condensate, inducing a vacuum. When the vacuum
breaker opens, atmospheric air and condensate mix inside the exchanger, increasing the
possibility of corrosion of the tubes, shells, tube sheet and tube supports.
Freezing - Steam/air coils cannot afford poor condensate drainage,
especially if the coil experiences air below freezing temperature. Condensate backed up
inside the coil will freeze, often within seconds, depending on the air temperature. A low
temperature detection thermostat is recommended on the coil leaving side to sense freezing
conditions.
As we previously explained, the only way to avoid "stall" is to eliminate
back pressure on the steam trap. There are a number of options available for designing a
system that greatly reduces the risk of "stall." The following are two such
options:
Install the
heat exchanger in a position so that the condensate freely drains by gravity to the
condensate return line. In many cases this is not possible because of existing piping
around the area in which the heat exchanger is needed (e.g., the heat exchanger is
installed at a level lower than the condensate return tank).
Use an
electric or pressure driven condensate pump package installed below the steam trap to pump
condensate back to the boiler.
In actual practice, the first option may not be possible, and so the use of electric or
pressure driven pumps to return condensate to the boiler room should be considered.
ELECTRIC PUMP PACKAGE
Figure 1 illustrates a typical piping system for a steam heat exchanger draining into an
electric condensate pump package. In this scenario, the steam trap is allowed to operate
over the entire load profile, as there is no back pressure on the steam trap. As steam
enters the exchanger, there will always be a positive pressure on the inlet side of the
trap, allowing condensate to flow through to the pump receiver. If a vacuum should occur
inside the exchanger, then the vacuum breaker will eliminate the vacuum by introducing
atmospheric air into the exchanger. With the steam trap installed 15" below the
exchanger, this will give a 1/2 psi hydraulic head before the trap, creating the
differential pressure necessary to drain condensate from the exchanger.
Electric condensate pumps offer a number of advantages that often make them the
preferred choice among engineers:
Engineers
are familiar with their operation and ease of maintenance
There are many
different options available to meet custom requirements
Iron or steel
receivers are available
Relatively
small units with low profile equate to smaller required installation space
A wide range of
sizes are available, catering to diverse applications
They can
deliver large capacities over wide ranges of back pressures
They can accept
condensate flow during the pumping cycle
PRESSURE DRIVEN PUMPS AND OPEN SYSTEM RETURN
Another option to ensure proper condensate removal is the Pressure Operated Pumpless
Condensate Unit. This type of pump uses steam or compressed gas (air) as a "motive
force" to create the differential pressure needed to transfer the condensate. There
are no impellers, seals, or electric motors used with the Pumpless Condensate Unit. ITT
Domestic offers this type of unit under the model name PCC.
The Pumpless Condensate Unit uses a float mechanism to operate the pump cycle. This
float mechanically connects to an exhaust valve (normally open) and a steam/air valve
(normally closed). Condensate flows by gravity through the inlet check valve into the pump
body. Air vents through the exhaust valve, allow the pump to fill. As the pump fills, the
float rises. At a predetermined level, the float mechanism opens the steam valve and
closes the exhaust valve, introducing steam or air into the pump. As the pump pressurizes,
the inlet check valve is forced closed, and the condensate is pushed out of the outlet
check valve and into the condensate return piping system. When the pump empties, the float
switches the position of the steam and exhaust valves, and the cycle begins once more.
The Pumpless Condensate Unit does not function as a steam trap; the pump
cannot discharge condensate while holding back steam. The ability of the pump to operate
and the capacity it can handle are functions of:
The
differential pressure between the motive force and the pressure in the condensate return
piping
The check valve
sizes
The height
difference between pump and receiver
The operation allows the pump to accept condensate during the filling cycle only. As
the pump discharges, condensate stores elsewhere until the discharge stroke is complete.
For this reason, a receiver must be installed before the pump. The receiver should be
sized for the amount of condensate that will form during the pump's discharge cycle. The
receiver stores the condensate, eliminating the possibility of backing condensate into the
steam space of a heat exchanger. The vent line on the receiver must be sized to handle the
flash steam created as hot condensate discharges from the steam trap(s) into the receiver.
An undersized vent line creates pressure inside the receiver, raising back pressure
against the trap. The height of the receiver relative to the pump is important. The pump
fills up with condensate fed from the receiver. A minimum distance of 12" from the
bottom of the receiver to the top of the pump is required to provide the pump's rated
capacity.
At distances greater than 12", the capacity of the pump increases because the rate
at which condensate flows from the receiver to the pump is a function of static head.
The size of the inlet and outlet check valves also influences the pump's capacity.
Standard options are l"x1", 2"x2", and 3"x2" (inlet size by
outlet size). The larger the valves, the higher the capacity.
Differential pressure between the motive force and the return line has the largest
influence on pump capacity. The larger the differential pressure, the higher the capacity.
The Pumpless Condensate Unit operates similar to a steam trap with regard to differential
pressure and capacity. The larger the difference between motive pressure and system back
pressure, the higher the capacity of the pump.
Figure 2 illustrates a typical pipe-in of a Pumpless Condensate Unit and a steam heat
exchanger. The Pumpless Condensate Unit is sized to handle the condensing rate of the heat
exchanger. The maximum motive pressure recommended is 125 psi (100 psi is usually more
than enough; it also eliminates the possibility of water hammer inside the pump that is
sometimes present with a 125 psi motive force). A steam trap is installed at the inlet of
the motive force to remove condensate that forms while idle steam condenses in the line
during the filling cycle of the pump. The vent line from the Pumpless Condensate Unit is
tied into the vent line of the receiver. An overflow pipe, installed below this tie-in
point, allows condensate to drain should the receiver be undersized or the pump fail to
cycle.
This overflow connection is important in preventing condensate from backing up into the
steam space of the exchanger and also warning the operator that possible problems exist in
the system.

|
A pressure gauge should be installed on top of the Pumpless Condensate Unit to help
diagnose any problems, and to help estimate condensate flow and back pressure. This gauge
assembly should include these components:
Gauge
Pigtail siphon,
used to prevent live steam from entering the bourdon tube which could cause damage to the
gauge
Isolating valve
(normally closed), limiting wear and tear on the gauge when the operator is not using it
Pressure
snubber, used to dampen pressure shocks experienced with the sudden introduction of motive
force
During the fill cycle, the pump vents to atmosphere and the gauge should read
"O." As the pump cycles, the gauge will read a pressure reflecting the return
pipe system pressure. The gauge is also useful to display the cycle's length and
frequency, as well as the back pressure on the system.
An open Pumpless Condensate Unit system (as shown in Figure 2) offers a number of
advantages:
Condensate is
removed as it is formed inside the heat exchanger
Single trade
installation is afforded because electric power is not required
No electrical
energy is consumed
There are no
seals to wear out and replace
There are no
cavitation problems because there is no impeller
A wide range of
capacities and motive pressures are possible
Internal parts
are easily replaced without any interruption of piping
An excellent
solution within hazardous environments is afforded because electricity is not involved.