Maintenance TipsA manufacturers
pump performance curves contain data that can help hvac technicians analyze a pumping
installation. Pump curves also help identify the systems operating point, find
reasons for a system not performing, and even determine a pumps impeller size.
After designing a pump, the manufacturer usually produces a number of units for testing.
The tests are necessary to establish how the pump will perform. The data collected often
includes water flow operating against various system resistances, brake horsepower
required, efficiency, and the net positive suction head required for proper operation of
the various diameter impellers allowable in the pump volute.
This data is analyzed and then plotted and published as the pump operating
characteristics. The pump curve then shows how the pump will perform with varying head or
flow requirements. (See Fig. 1).
 |
Figure 1. The pump curve shows how the pump will perform with
varying head or flow requirements.
|
In the real world it isnt unusual for a pumps nameplate to
be missing. Because the information on a nameplate is so important (it usually includes
manufacturers name, pump model, size, impeller diameter, head and flow for the duty
point), its frequently removed for safe keeping. Unfortunately, at times its
so well safeguarded that it cant be retrieved. Or, perhaps its just painted
over. Either way, the information on it isnt available.
To identify the pump and reestablish the nameplate data, the manufacturer must be
determined. Most pumps are fabricated of castings and most of these have casting part
numbers and markings on them which identify the pump manufacturer. Once the pump
manufacturer is known, the type or model and size can be determined with the help of
published literature or a phone call.
Since larger pumps generally have a family of impeller sizes which can be used with a
given pump body, at this point the impeller diameter is unknown. A simple procedure using
a pressure gauge and the pumps curves will identify the impeller size in the pump.
Identifying Impeller Size
Close the pump discharge valve and take the suction and discharge pressures. This is the
dead-head condition. Reopen the discharge valve and reset it to the position
it was in prior to closing, if it was used to balance the flow. The algebraic difference
between the discharge pressure and the suction pressure is the head being generated by the
pump. Convert this to feet of water head and determine the correct impeller from the no
flow point on the pump curve. As an example:
P discharge = 20.5 psi
P suction = 4-in. of Hg vacuum (a negative pressure) But, the curves are dimensioned
Head, feet of water therefore, the gauge pressures must be converted.
To convert pressure in psi to head in feet of water multiply psi by 2.31 and divide by the
specific gravity of the fluid being pumped. The specific gravity of water is 1. One inch
of Hg is equal to 0.491 psi.
Therefore:
P discharge = 20.5 psi x 2.31 ft. of water
per psi / (divided by) 1 = 47.4 ft. of water
P suction = 4 in. Hg x 0.491 psi per in. Hg = -1.96 psi x 2.31 ft of water per psi/1= -4.5
ft. of water Pump head = P discharge - P suction = 47.4 - (-4.5) ft. of water
Algebraically subtracting a minus is a plus, so:
Pump head = 47.4 + 4.5 ft. of water = 51.9 ft. of water.
Locating this head, 52 ft., at 0 gpm flow on the pump curve in Fig. 1, shows the pump
impeller diameter to be 7 in.
The system operating point can also be determined by using gauge readings. Take the
suction and discharge pressures while the system is operating with the discharge valve in
the normal open position. Again convert these into feet of water and subtract
(algebraically) the suction pressure from the discharge pressure. This is the head of the
pump at the operating flow. Follow the head line from the zero flow axis out to where it
intersects the previously identified impeller characteristic curve. The flow at that point
is the systems operating flow.
Example: After determining the pumps impeller diameter to be 7 in., gauge readings
of the pump taken while it operated were:
P discharge = 17.5 psi
P suction = 4 in. Hg (vacuum)
Convert the gauge readings for the fluid being pumped to feet of water: P discharge = 17.5
psi x 2.31/1 = 40.5 ft. of water
P suction = 4 in. Hg x 0.491 psi per in Hg = -1.96 psi x 2.31 ft. of water per psi/1 =
-4.5 ft. of water Pump head = 40.5 - (-4.5) ft. of water = 45.0 ft. of water
The pump head of 45.0 ft. intersects the 7 inch diameter characteristic curve at 55 gpm,
which then is the system operating flow.
Being able to fully identify a pump, determine the installed impeller size and the system
operating point are of great use in troubleshooting.
As an example:
 |
Figure 2. Depicted here is a two horsepower base-mounted pump
which regularly trips its circuit breaker. The top graphic depicts a coil configuration
and the bottom one, a bypass.
|
The 2 hp base-mounted pump in Figure 2, when pumping water, regularly
trips its circuit breaker. The nameplate specifies an 81/ 2-in. diameter impeller with a
duty point of 51 gpm at 74 ft. of head. Gauge readings at shutoff are 12 psi suction
pressure and 46 psi discharge pressure. When the 3-way valve is fully open to the coil,
the suction pressure is still 12 psi and the discharge pressure is 44 psi. When the 3-way
valve is fully open to the bypass, the suction pressure is still 12 psi, but the discharge
pressure is 40 psi.
Whats the problem? Whats the solution? First, you must analyze the pump
readings.
Shutoff head is (discharge pressure -suction pressure) x 2.31 = (46 psi - 12 psi) x 2.31 =
78.5 ft. of water
The 78.5 ft. at shutoff and the pump curve (Fig. 1) confirms the impeller diameter as 81/
2 inches.
With the 3-way valve fully open to the coil:
Pump head = (44 psi - 12 psi) x 2.31 = 74 ft. of water The intersection of 74 ft. of head
and the 81/ 2-in. impeller curve on Fig. 1 indicates a flow of 51 gpm. The horsepower
required is 13/4. With the 3-way valve open to the bypass, the pump head is calculated as
follows: Pump head = (40 psi - 12 psi) x 2.31 = 64.7 ft. of water.
The intersection of 64.7 ft. of head and the 81/2 inch impeller curve on Fig. 1 indicates
a flow of 80 gpm. The horse-power required is 21/ 3.
The problem - too much flow because the resistance to flow in the bypass circuit is too
low.
The solution - increase the resistance in the bypass circuit by 9.3 ft. of water (74
-64.7) so the resistance through the bypass circuit is the same as the resistance through
the coil. The flow and the horsepower will then be reduced to the same as that flowing
through the coil, eliminating breaker trips.
Understanding the information provided on the pump curves by the pump manufacturer and
taking some simple gauge readings are of great help in analyzing pumped system problems.