When a modern hot water boiler experiences thermal shock,
the cause is often ignored and written off as defective material or workmanship. But there
is always a reason why a boiler (cast iron, steel fire tube or steel water tube) becomes
thermally shocked. "Boiler Thermal Shock" can be loosely defined as sudden
thermal changes that occur within the boiler causing rapid and uneven contractions of the
boiler's cast iron or steel material. An example is placing a cold glass under hot water
-- the glass cracks because of the extreme temperature change. In thermally shocked
boilers, the fractures or cracks occur where the temperature difference is greatest --
usually in the back of the boiler near the nipple joints or the furnace area where the
cold water enters. Surfaces exposed to cold water are contracting while surfaces exposed
to fire are expanding.
Causes of Boiler Thermal Shock
Several
conditions can contribute to boiler stressing and eventual boiler shock. All involve
introducing excessively low temperature water, or cool temperature water at high flow
rates, into the hot boiler:
Returning
water at too low a temperature
Cool
return water at too great a flow
Firing
the boiler and heating up water before system circulator is turned on
Moving
the burner into high fire with boiler water at too low a temperature
Influence of System Designs
Systems
incorporating night setback and/or weekend shutdown are designed to save energy, but
turning down or shutting off the building's temperature causes problems when all the zone
valves and pumps come back on delivering room temperature water to a hot boiler.
Dual
temperature changeover systems can experience boiler problems when the system tries to
change over from a cooling demand to heating. The piping system and terminal units are
filled with 50 - 60°F water and the boiler may contain 180°F water.
Heat pump
loop systems typically require some form of supplementary heat to maintain supply water
loop temperatures when the outdoor temperature approaches design conditions. Boilers are
the common source for this additional heat, but design loop temperatures are as low as 70
- 85°F, while most commercial cast iron boilers dont operate below 140 - 150°F.
Heating
systems that have boilers maintaining temperature without flow are susceptible to thermal
shock by sudden changes in flow due to pump operation.
The most
common cause of thermal shock is a system that incorporates outdoor reset with 3way valves
while the boiler maintains temperature. The boiler is at 180°F, but based on outdoor
temperature, the system may require only 100°F. The return temperature can be as low as
90°F, which can cause a 90°F differential across the boiler. (Remember the cold glass
and hot water!) Most cast iron boiler manufacturers would like to see no more than a 40 -
50°F temperature difference between the boiler's return temperature and leaving
temperature.
Preventing Thermal Shock
Waterside thermal shock can be prevented by controlling the load imposed on the boiler.
Boiler load is a function of flow rate and temperature difference, and one of the most
effective methods is to create a boiler loop separate from the system and pump it with its
own circulator. Since the flow rate is constant, the temperature difference across the
boiler becomes the measurement of the boiler's load, and if the boiler is maintaining
temperature, the return water's temperature will determine the boiler load. Control
against "boiler shock" involves control of the incoming cold water flow rate so
that the boiler's temperature is changed slowly. By installing the 3-way valve in the
boiler loop, the outdoor reset can control the amount of hot water that is introduced into
the system based upon a reset schedule. More importantly, the reset controller can measure
the return temperature entering the boiler. If water temperature becomes too low for the
boiler manufacturer's recommendations, the 3-way valve will close off the system loop. Hot
water from the boiler will then be pumped right back into the return, raising the water
temperature entering the boiler. The 3-way valve and controller will float back and forth,
resetting the supply water to the system while protecting the boiler from cold water.
The best method for interconnecting this boiler loop with the system loop is through
primary/secondary pumping techniques. By keeping the supply and return tees close
together, the pressure drop in the common piping is kept to a minimum. This allows
different size pumps to coexist in the system without affecting each other as well as
preventing ghost flows from occurring from one loop into the other.
For more information on this or any hydronic subject, contact your local Bell & Gossett
representative. They can help soothe your shock, so give them a call.