|
[ Search main FAQ's database for
answers ] [ Ask a Technical Question ]
Return to Bell & Gossett web site.
Helpful Hint: to search
this page click ctrl+F
Q: Dear Red: General comments on pro/con re draining a baseboard hot water
system over the winter in a vacant house? 2 story with some plaster walls.
A: The concern with draining the system is that the pipes house will get below
freezing temperatures. The water in any part of the house will expand and could burst
pipes, fixtures, ect. All water pipes would need to be completely drained and left open to
prevent water from gathering in the pipes and possible freeze-up. If the hydronic heating
system is drained, next year when it goes back on, good practice will need to be followed
to assure that all air is purged, etc. I would recommend contacting a heating and plumbing
professional to assure that nothing is overlooked. P.S. During the winter time, Red leaves
the heat on at the summer house. Red just turns the thermostat down so not to use up to
much energy and keep the cost down. But high enough to keep pipes from freezing.
Q: Dear Red: I have a Federal boiler with a Bell & Gossett
series 100 pump on it that runs the water through the pipes in my heating system through
the house. In the winter time when I start using the heater there is a seperate switch to
turn on the series 100 pump. The question I have is why would this pump need to run all
the time and should it run from October through February? If that is the way it is
designed that's okay I just wanted to know if there was some shut-off switah that was not
installed in the system.
A: Running the pump throughout the heating season is one way to operate the
system. It provides flow all the time, so there may be less noise due to start-up, and you
are using the residual heat from the boiler after it shuts down. More often, the pump
starts when the thermostat calls for heat. Ask local Bell & Gossett dealer about our
pump control packages if you want to change it. Having a switch near the pump is a good
idea if someone must service the pump.
Q: Dear Red: I have a 100,000 BTU propane boiler servicing a
single zone baseboard heating system in the house this has 40,000 BTU approx excess
capacity. I would like to take the chill out of the basement using a fan assisted coil
unit. Can you recommend a suitable unit and advise if I will need another circ pump and
zone valve. The volume of the basement is 40 x 40 x 12 and stays at 45 to 55 degrees
summer and winter.
A: If you are sure that the existing boiler has extra capacity, then you can
easily hook up another terminal (of any kind) to heat the basement. If your existing pump
can handle the increased flow, you could simply install the new unit with an electric zone
valve. If the existing pump is on the small side, add a separate zone with pump and
thermostat to heat the basement. Ask the people at our local B&G representative about
adding B&G Flo-Controls. These devices protect the zone from unwanted heat due to
gravity circulation into the idle zone. You may not need them if the basement zone
elevation is lower thn the source of hot water.
Q: Dear Red, We have a steam radiator system in a 90-year-old
house. On our 3rd floor bedroom when the steam starts to come up we are treated to bangs
and clangs galore. This winter the heat emanating from the radiator diminished, then quit.
Today, my husband put on a new air vent, and fiddled with the valve, but there was no
improvement. Then he disconnected the radiator, turned up the heat, and we watched. We
heard gurgles and burps, but no steam. Then I jiggled the pipe (it runs down through the
flooring, then nearly horizontal through kneewall/ attic space, then down to the
basement). Then loud gurgles, then the pipe spit up about two cups of water. Then steam
came whooshing out! We are warm again. How do you explain this and what do you recommend
for maintenance?
A: Based on what you told us, you have a one-pipe steam system. (Only one pipe
connection, and it's at the bottom of the radiator, an air vent on the other side.) It
sounds like that "nearly horizontal" pipe run is the culprit in this mystery.
It's supposed to be pitched so that condensate from your radiator drains back to the
boiler, even though steam is going the opposite way in the same pipe toward the radiator.
Suppose that vertical leg leading to the radiator dropped a little so that the horizontal
leg was pitched away from the boiler. Water could accumulate in the horizontal leg, and
block the steam flow. If your "jiggling" resulted in lifting the pipe so that
some of the trapped water drained back, then the difference in pressure between the steam
and the atmosphere could blow the remaining water (two cups) out of the pipe, and you have
heat. If this is the case, then the solution is to insure that the pipe stays pitched
properly. There may be other factors we haven't discussed, so it would be wise to have a
qualified contractor look at the system.
Back
to Top
Q: Dear Red, We have a old house, built about 1905, that has
an American Radiator Hot water boiler system. The system has alway been a gravity
recirculating system, another words, no pump. The house is large, about 3500 square feet,
not including basement. There are three stories. Basement has no radiators. First floor
has four radiators, second has four and third floor has three. Both the supply and return
pipes, all of which are threaded steel pipe, at the boiler are 4", though they are
only that size for a few feet until they split into the four risers and returns. The
risers/returns are sized from 1 1/4 to 2". My question is...How do I size a pump and
what controls do I need to have to make this pump work most effectively. Can I use a
2" flanged pump? What is meant by "feet of head" in a two pipe system? Do I
install this on the supply or return side.
A: This is such a common question that we have worked up some example problems
which we cover in our "School of Living Comfort" hydronics design seminar. We go
into a lot of detail about the science and the art of making this kind of conversion. It's
that word "art" that causes the problem here, because there's a lot of detail to
consider, and it's impossible to cover all that in this short reply. If you contact the
Bornquist, Inc. people, they can arrange for you to attend one of our seminars, free of
charge. That way, you'll get the whole story. If you can't make it, here are some shorter
answers to your specific questions. A 2" pump would certainly be in the right ball
park, since any pump will provide a lot more "head" than the gravity system
provided, and consequently, you don't need such large diameter pipes. As to the exact
sizing of the pump, that requires a little more detail. Come to the seminar, or talk to
Bornquist for specifics. "Head" in referring to pumps, is the amount of
mechanical energy that the pump can put into the water to make it flow through the pipes
at an acceptable rate. Think of head as foot -pounds of energy per pound of water. Each
pump has its own head vs flow capability curve. Always install the pump so that it is
pumping away from the point where the compression tank connects to the system. (That's
another detail we cover in the seminar--sizing of a new closed tank to replace the old
open or closed tank your system may have.) Since the tank is often connected at the
boiler, this amounts to pumping away from the boiler, or putting the tank on the supply
pipe. Once again, it's a bit more subtle than that, and if you can get to the seminar, we
can clear up a lot of misunderstandings.
Q: Dear Red, I recently installed a new high-efficiency boiler
in my house. The old boiler had 2 supply and return lines going in and out of the old
boiler; each line has a B&G PR series pump. The new boiler has only 1 return and 1
supply outlet so the 2 supply and return lines had to be teed into the new boiler. Since
the new boiler has been installed I can no longer get any heat out of two basement
radiators that are at the end of each loop. I gutted the 2 check-valves and this helps a
bit but I still can't get hot water completely through the two end radiators. If I shut
down one of the loops I can get hot water through the end radiator on the open loop.
A: A couple of things could be happening to explain why you're not getting
heat at the end of those loops. Call our representative, to help find a qualified
contractor to help you solve this. Here are a couple of things to check. 1. Is the new
boiler big enough? If it doesn't have enough heating capacity, the end radiators won't get
hot. Since you can get heat when you shut off one loop, this may be the case. 2. You could
have air trapped in the radiators. If the new boiler has a lot more pressure drop than the
old one had, there may not be enough velocity in those radiators to pick up the air and
bring it to the point of air separation.
Q: Dear Red, I have a gas boiler (radiator heat) with two B
& G circulator pumps/boosters. The main circulator was here when I moved in 21 years
ago (the house & boiler are 45 years old) and has the following noted: 17 amps, 115v,
11/12 hp, Ser # 101-5-1-M, 1725 rpm The other circulator was installed about 19 years for
the second floor attic conversion (2 zone heat) and has the following: Series # 100,
106189, 225-245 degrees. I am looking into purchasing a backup generator and need to know
the recommended start up and continuous running amps/watts for each circulator.
A: Both circulators should have very similar Amp and Watt input values. The
locked rotor (start up) Amps will be in the 12.0 Amp range. The continuous run conditions
will be approximately 1.7Amps/130 Watts.
Back
to Top
Q: Dear Red, I am having a little trouble with my Hot water
baseboard heat. I have a 2-story home that has 2 zones. 1 upstairs & 1 down. I
recently was getting a lot of noise from my impeller area. I talked to a local supply
house and we decided to remove & bring my motor/pump assembly in for inspection. We
found the motor to be tired. We replaced the motor, bearing assembly, and impeller (all
B&G parts). Since then, I have been having trouble getting heat to flow to the
upstairs. I find that I get heat to the upstairs, but that there is no flow. I have purged
the lines for air, and also, turned off the downstairs zone, forcing the system to
circulate only the upstairs (I will call it zone 2). As long as zone 1 is off, I get great
circulation through zone 2. When I open zone 1, zone 1 gets all the circulation. Is there
a simple procedure I can use to balance the flow between the 2 zones?
A: You say you're getting heat, but you have no flow. I'm not sure how you're
doing that or determining it. But based on the information you've included, I'd say that
when the bearing assembly was replaced, that a balancing valve must have been closed to
service the pump. Something had to have happened when the pump was replaced that upset the
balance between the two zones, assuming there was no problem before. Somehow zone 2 now
has a much greater pressure drop than before. To balance the system you have to determine
the flow rate you require in each zone. Then you need to determine the pressure drop
through each zone when the valves are open. Finally, you would ideally add pressure drop
to the zone with the lower pressure drop to equal the pressure drop of the higher-pressure
drop zone through the use of a balancing valve. To make it simpler, look at zone 2, and
ask yourself what you can do to lower the pressure drop in that zone. If that does not
balance the system, look at where you can add pressure drop to zone one until the two
zones are equal. Retrace what you did before you replaced the bearing assembly, I'm
willing to bet that is where the trouble occurred - a valve accidentally got closed and
was not returned to it's original position. Once you do that, I'm sure the problem will
jump out at you. If none of these works, ask the local representative to stop by.
Q: Dear Red, While on vacation the water company shut off our
water (long story). The water ran out of our operating Slc-30 circulator pump. A neighbor
heard the noise from outside our house (sucking air, burning the pipes/pump) He turned it
off. The plumber replaced the side pipes but thought the pump was still good. When
running, it made a loud humming noise. He came back out said the pump was bad and not
worth re-building. He replaced the pump, now the same noise is louder and we have to turn
off the pump at night. He came out again and flushed the lines, still the same noise. He
says something broke off and is in the system. Now he wants to charge us by the hour to
clean out the lines. Do you know what is causing the hum, for 5 years we never heard the
pump inside and it working perfectly? This has become very expensive and after $500.00 we
are thinking of turning off the system and wasting water in our one story house to get hot
water.
A: Something in your system must have change to cause the humming sound. There
are a lot of unknown facts in your letter. Why did the city turn your water off? Did the
system pressure change? Did the pipes in your system change in diameter or type? Did the
plumber replace the SLC with a comparable circulator? Is there a pipe rubbing on a beam
somewhere? These all could have an effect on your system that is causing the noise. Contact your local B&G
representative.
Q: Dear Red, When weather is real cold in uninsulated old
house, with one pipe steam,is it unusual for boiler to cycle off presutrol and not reach
temp. after max pressure is reached ,what is normal leak down time for pressure to drop to
low cut in. If fire is to large a nozzele will this cause to run off presurtrol and not
reach temp. Only a few degrees lower than normal . Usually run at 72 but with 5 degree
weather settel for 68 degrees.
A: A short cycling boiler in a one pipe steam system is often caused by end of
main vents that are no longer working. As steam pressure builds, air in the system can't
escape through the vent, so the burner shuts off on high pressure long before steam gets
to the radiators. See our local
representative for help in getting those main line vents replaced.
Back
to Top
Q: Dear Red, I have a Hydotherm furnace with a B&G 100
series pump. The house is piped for two heating loops, using zone valves. I have baseboard
units in all rooms except for one which has original equipment. An array of baseboard
convectors piped in series and stacked in a loop. These are connected to the main heating
loop with scoop tee's. After recently replacing the bearing assembly on the pump and
bleeding as much air from the system as I could, I get no heat from this unit. All other
rooms have baseboard units in series, NO scoop tees and heat up fine. Could this assembly
be air bound? How can I solve this? Should I cut the loop between the scoop tees and
insert a valve to force the hot water in this unit?
A: If the system worked before, it ought to work again, especially if the only
change you made was a new bearing assembly for the pump. If you have manual air vents on
the convector assembly, try venting the air. Restore the system pressure by using your
pressure reducing valve to add more water after the venting.
Q: Dear Red,I have an American Standard G29,Series 7BN-J6
boiler.All my parts are B&G SA11/4 flow control valve;SA 3/4 flow control valve; ATF
Airtrol valve below expansion tank;2 series 100 circulating pumps up and downstairs;Relief
valve 175 set at 30lbs and inlet is3/4;Can't read valve where water comes in from outside
source because of drip from another pipe above separate from heating system.My question
finally is that the relief valve goes off and releases steam and water for a couple
minutes and what is causing this? The system has worked fine for 27 years.Shouldn't I see
the Temp drop in a couple minutes when the pump kicks on. The temp is high as 220degrees
but gauge doesn't go over 32lbs.Is it full of sludge?How do you drain it? The lines were
just bled twice. Lots of air first.
A: From what you've given me, I'd say that you have a waterlogged tank. So
lets get the system back to where it needs to be first. Let the sytem cool down to below
100 degrees. Ensure that the supply valve from the city is closed. Now open the Airtrol
Tank Fitting vent screw until the water level returns to normal. Assuming the correct size
ATF is installed, drain until no water comes out. Now you are back to the proper air to
water ratio in the tank. Now for why you lost your original air charge. When you bled the
air out of your system, you lost the room you had for the water to expand as it heated up.
Figuring how the air got from the tank into the system is not as important as ensuring
that once it is in the system that it is returns to the tank and remains there. The ATF
should ensure that the air remains in the tank. So you might want to check that. Next, to
ensure that any air in the system goes to the tank, check your air separator. You never
mentioned one. So if you don't have one, I'd recommend an Inline Air Separator or an
Enhanced Air Separator. See your local rep to determine which one would be the best for
your system based of effectiveness and cost. Also, make sure that you have no automatic
air vents in your system. Automatic air vents are used with pre-charged air tanks. For the
rest of your questions, I can not tell you if the temperature should drop until I know
where you're looking at the temperature. To drain your system, ensure that the city water
supply is close, open the drain valve. Opening a vent will help drain the system. To fill
the system, close the drain, open the city supply, use a Pressure Reducing Valve. Bleed
out the air through the vents. Open the tank fitting vent until you see water come out.
Now you have the proper charge. To clean your system, ask your local supply warehouse for
what would be the most effective materials based on your system. Make sure that he knows
about the pumps seals so that there is not a compatability problem. However, you probably
will get rid of most foreign materals when you drain the system. If the system is truely
closed, draining it will introduce oxygen, hence corrosion, so you don't want to do it
unless you have to.
Back
to Top
Q: Dear Red, I have never been able to get hot water to one
radiator upstairs; it's the furthest from the pump. I have bleed the system countless
times and can never get Hot water up there. Any suggestions? My house is 50 years old, but
the system is only 20. I am thinking a small separate in-line booster pump in the line
going upstairs from the crawl space might be a good fix? Any suggestions?
A: If you have tried to bleed air out of that radiator, and you dont get
any air, then the most likely cause is inadequate balance. Probably some of your closer
radiators are getting far more flow than they need, starving that farthest one. Install a
Bell & Gossett balancing valve in the closer circuits to reduce flow there and force
the water out to the farthest one. If you do get air every time you bleed that farthest
radiator, then you have an inadequate air separator or compression tank system. This could
easily tie in to the system pressurization problem you brought up earlier. Our local B&G representative. has
some excellent technical material that covers these problems. Ask him for TEH 1196, Air
Management.
Q: Dear Red, We have a Series SLC-25 circulator that was in
place when we purchased out house. We don't know anything about it. We were told by a
neighbor that it gives you hot water as soon as you turn on the tap. We've noticed that is
not the case. There is no noise of vibration coming from it, however, the unit itself is
always hot. We located a small knob on the side of the unit, but are unsure about which
direction to turn it. It appears to be a fairly expensive item and we would like for it to
work. Also... there is a 110 plug configuration that concerns us. The unit is plugged in
and we have concerns about safety.
A: It should be a bronze bodied pump. It's designed to recirculate hot water
through the system so you don't have stagnant, cool water after a period of no demand. The
pump may be hot because it's installed so close to the water heater. If it's not pumping,
check to insure that power is available in that circuit. The knob you see is the speed
setting. Turn it to position #1, the highest speed, then feel the pipe coming back from
the system, if it heats up, the pump is working properly. If it doesn't, call the Bell
& Gossett representative nearest you. You can look them up on our web site, or in the
yellow pages. About the electrical connection, if it doesn't look right to you, by all
means call an electrician right away.
Back
to Top
Q: Dear Red, I live in an old house heated by hot water
radiators driven by an oil-fueled Columbia boiler with a circulating pump. It was
installed in 1976. The house was previously heated by a coal furnace. In the last few
years, there have been more and more frequent problems with getting all the radiators
heated. Those on the end of the water circulation path (as told by the service technician)
go cold when the weather gets a bit warmer and the furnace doesn't run as frequently. They
consequently would not heat up when the weather got colder again. In the last 2 years,
usually only one radiator will be hot û the one that is at the beginning of the
circulation path. The only way to get most (or all, if we are lucky) of the radiators hot
is to drain the entire system and refill it. When done, the furnace will run consistently
and all the radiators will be heat up for a 1-4 days. They will all gradually cool off,
and the furnace will only in 5-minute bursts regardless of what the thermostat (also,
original from 1976) is set at. We can get the one radiator at the beginning of the
circulation path hot by bleeding it. It is the only radiator in the house that has its own
bleeder valve. There is a ôMaid OÆMistö valve on a pipe in the attic that is supposed
to vent out the air for the rest of the system. This has been replaced a number of times
the last few years. I just wonder what can be the cause of these more and more frequent
heating problems with faulty aquastat, bad thermostat, poor water circulation, weak/old
boiler?
A: It sounds a lot like an air problem that gets progressively worse as time
goes on. If you refill the whole system, you can get heat throughout, so the pump and
boiler sound OK. That vent up in the attic just isn't designed to control air as it
should. The details are a bit lengthy for the internet, but a qualified contractor could
provide the air separator you need and take a look at the existing tank to make sure it's
right too. Contact your local
representative for this detailed help. You can find them on the web.
Q: Dear Red, Let me paint you the picture. I live in a
Colonial style house of approx. 1600 sq. ft. built in the 1941. The heating system is
single zone hydronic and employs a 150,000 BTU gas fired boiler circa 1977. The circulator
pump is a B&G series 100 (other label markings include FW and 142 if this helps). The
piping system starts out at 1 1/4" and routes to the in-wall cast iron radiators on
each floor. My problem is that when the system is cool (e.g. warm days/cool nights in
spring and fall) and the thermostat calls for heat, the system takes about 40 minutes for
the radiators to warm up at all; obviously an inefficient way to raise the temp by only a
few degrees. I have noticed that even when the boiler runs (circulator runs too) for a
while the delta temperature from the inlet to the outlet of the boiler is negligible. I
theorize that the flow rate through the boiler it too high, not allowing sufficient heat
transfer. Does it make sense for me to try a lower GPM circulator pump? If so, any
suggestions? Does my theory hold water, or is this Electrical Engineer all wet? (No pun
intended.... O.K. maybe a little). Also, do you know where I can get the curves for this
pump? I couldn't find them for this model on your site.
A: I think that the keyword in your story is cast iron. It takes a while to
heat up all that thermal mass, and that's what you're seeing. On the other hand, once you
get it warm, it takes a long time to cool off, so you get the benefit as well. You might
look at your thermostat location. If it's not seeing a good average temperature, maybe it
could be re-located. The pump was designed for exactly you're kind of system--relatively
large flow rates, and relatively low head loss. I wouldn't change it, since it wouldn't
have an impact on the problem you're posing. The curve for the Series 100 Booster is
included in the Hydronic Specialties Booster Pump curves--a series of similar pumps all
displayed on the same coordinate axes.
Back
to Top |